Optical length measurement
For the purpose of obtaining an accurate measurement, the refractive index of the installed optical fibers must be considered. This measurement must be performed using an OTDR, properly calibrated and certified by the manufacturer or authorized distributor. The resulting measurement values must not exceed, in the case of fusion splices, an average of 0.15 dB per splice measured bidirectionally, and 0.5 dB per connector pair installed along the fiber path under test. The theoretical value considered for power loss per kilometer is 0.38 dB for fibers measured in the second window (1310 nm) and 0.25 dB for fibers measured in the third window (1550 nm).
The measurement should be carried out with the best possible resolution, that is, the distance and pulse width value should be the smallest possible.
Attenuation measurement[edit]
For the measurement, two fiber optic launch reels of a length of no less than 1000m must be used and each reel will be of the same fiber optic technology used by the pig tail cords.
In order to perform the measurement, one end of the coil must be pre-connected with the same type of connector used at the fiber distributor level.
Reflection measurement
The return loss values measured at each fiber optic cable termination at each fiber optic distributor level must comply with the following standard:
70% of measured values > 40 dB (higher)
30% of measured values < 38 dB (lower)
Measurement of total path loss by optical power
The total loss of each section ('A') for each optical fiber must satisfy the following equation:

Being:
'A' = Total segment loss (dB)
'a' = Nominal attenuation of the optical fiber at the specified wavelength (dB/km)
'L' = Total optical length of the segment (km)
'En' = Total number of splices. Drop splices, if any, and pigtail splices are not considered.
'ae' = Average attenuation value per splice (dB)
'Nc' = Number of connectors.
'ac' = Connection loss at the distributor level (dB)
For the calculation, the following values must be considered:
'a' = 0.25 dB/km at 1550 nm and 0.38 dB/km at 1310 nm. Standard single-mode optical fiber.
These attenuation values should only be considered if they correspond to measurements taken on the cable prior to installation.
'L' = optical length. For measuring the optical length of the section, the refractive index corresponding to the installed fiber must be strictly considered.
'ac' = 0.25 dB for LC, SC, ST, and FC connectors.
Considering the possibility that the instrument's physical interface may not be compatible with the connectors used at the fiber distribution point, the following calibration procedure will be necessary for power measurement, as it requires two adapter cords for the transmitting and receiving instruments, respectively.
The transmitter's output power level will be measured using a cord connected according to the instrument's physical interface.
The insertion loss of the connector set corresponding to the interconnection of the two matching cords will be measured.
The intrinsic loss will be the difference between the measurements taken in the previous steps and must be less than 0.4 dB.
Using the configuration from the previous step, the transmitter-receiver equipment will be calibrated.
Due to this calibration equipment, 'Nc' = 1 must be considered in the calculation of the total path loss.
If the measuring instrument has an interface compatible with the connectors used at the fiber distributor level, the calibration will be carried out directly between the transmitter-receiver equipment, since it will not be necessary to use adaptation cords.
The interconnection step must be performed by disconnecting the reference cord at the receiving equipment. For measurement purposes, a fiber optic distribution equipment connection cord must be used.
Due to this type of calibration, 'Nc' = 2 should be considered in the calculation of the total path loss. The measurement will be performed at wavelengths of 1550 nm and 1310 nm.
The absolute value of the loss will be obtained as the average of 3 measurements taken after 3 disconnection-connection processes