To ensure uninterrupted availability 24 hours a day, Monday through Sunday, the company chose Eaton as its power supply systems provider.
With its two state-of-the-art data centers, Previder is one of the leading providers of ICT services, data centers, cloud services, and internet in the Netherlands. Opened in 2010, Previder's PDC2 center is the largest operator-neutral data center in the eastern Netherlands, with four independent rooms and a surface area of 2,500 m². While many data centers in the western Netherlands are located below sea level, Previder's data center sits 14 meters above sea level, ensuring a dry environment—a key advantage for many customers.
In addition to renting rack space, PDC2 users also have access to ample workspaces and meeting areas.
Simplicity and efficiency: how to plan the energy protection of a data center.
When Previder began designing the PDC2, it wanted to ensure its customers had a future-proof data center. This meant that certain issues regarding connectivity, power supply, and energy efficiency had to be carefully considered, utilizing the latest technologies.
Previder chose Eaton to install the entire electrical system. They selected Eaton's turnkey system, which includes everything necessary for a functional electrical system, including medium-voltage switchgear, low-voltage switchgear for the main power supply and for the data center rooms, busbars or conduits, and UPS systems.
“We only had one meeting with Eaton, who quickly answered all our questions, and we were able to purchase all the equipment at once. Choosing Eaton’s turnkey system has saved us a lot of money and brought us significant economic benefits,” says Marco Alink, Installation Manager at Previder’s PDC2.
Project planning was carried out by Previder, Lesscher (the main electrical contractor), and Eaton. Installation and product application were performed in collaboration with Eaton and Lesscher.
Maximum uptime guaranteed.
Previder's primary concern is maintaining data availability and accessibility, so it focuses all its efforts on achieving this. "We want to achieve maximum redundancy," says Alink. "Whether it's a power supply issue, fire safety, or cooling: everything is checked multiple times. We leave nothing to chance."
The PDC2 Data Center has four individual rooms. Each one is physically isolated from the others and equipped with its own electrical, cooling, and fire control systems to ensure that a failure in one room does not affect the servers in the others.
At PDC2, the electrical supply system is a TIER3+ installation and is ISO 27001 certified. All main systems in each data room (such as power, emergency power, air conditioning, and network connections) are duplicated according to the N+1 principle. The redundancy standard used (N+1, N+2, and 2*[N+1]) ensures the elimination of all possible failures, thanks to a second or even a third backup system. The most critical systems have double redundancy (N+2).
Each data room has been designed with a 2N UPS solution, with two independent power outlets (A and B). As part of the project, Eaton provided the UPS system for data room 1, which has an IT load of one megawatt. The system consists of six 9395 UPS units, each rated at 550 kVA. Each power outlet has two UPS systems in operation and one backup (redundant). The system is 100% redundant: each power outlet is capable of providing sufficient power to each data room in the event of a failure on another outlet. The UPS redundancy is based on Eaton's Powerware Hot Sync® load-sharing technology, which allows the units to operate in parallel in a completely independent manner.
Each data room must have separate power supply outlets A and B. Each is equipped with two UPS systems in use and a third redundant one, ensuring that the data rooms are always available.
Result: Energy efficiency for an eco-friendly Data Center
To reduce power consumption and achieve maximum efficiency without compromising uptime, the UPS in Data Room 1 utilizes Eaton energy-saving technologies. Two distinct technologies are employed to distribute the risk of power failure. The UPS at power outlet A utilizes Eaton's Energy Saver System (ESS) technology, enabling the UPS to achieve 99% efficiency without sacrificing reliability, while power outlet B employs Variable Module Management System (VMMS) technology for optimal utilization of the UPS battery modules.
Under normal circumstances, both supply outlets are used simultaneously (2N). Each outlet operates at a maximum of half load. In the event of a total failure of one outlet, the other takes over the full load, still operating in the N+1 configuration.
The environment was a key consideration in the construction of the PDC2 data center. The goal is to achieve an Energy Efficiency Index (EEI) of 1.25 (meaning only 25% of energy is used for support systems). Many other data centers have an EEI of 2.0. This makes PDC2 one of the greenest data centers in the Netherlands. Previder uses exclusively green energy, and cooling is managed through an open, eco-friendly system.
Accessible and Available Data:
It took a year to implement the initial designs of the PDC2 project. Currently, the first data room is operational, and Previder will begin using the others gradually. In its future data rooms, Previder will use a UPS configuration similar to the one already in use. They also plan to build another data center in Hengelo, with a total IT capacity of 16 megawatts.

“We are very pleased with the final result delivered by Eaton at PDC2,” Alink concludes. “For us, maximum stability is a top priority, and that’s another reason why we chose Eaton. They have extensive experience in data centers and specialize in medium and low voltages. The excellent maintenance contracts and attractive pricing we secured for the entire project are proof of that. The positive experience at this center is a great prelude to building another identical data center here in Hengelo.”
Eaton turnkey system
Two Eaton ELatis distribution cabinet systems
Two Eaton Capitole 40 4000 A switchgear and control units
One Eaton Capitole 40 6300 A low voltage emergency switchgear and control unit
Two Xiria coiled cable stations
Transformers
Medium voltage switchgear at the main feed and Data Center room
Low voltage switchgear at the main feed and Data Center room
MEM busbars/ducts
TIER III+ installation (redundant transformers and 2N UPS solutions per unit/data room)
UPS system
- 6 x Eaton 9395 UPS, 550 kVA,
with Hot Sync®, installed in a
2N configuration (supply outlets
A + B).
- Each N+1 supply outlet =
3 x 550 kVA Outlet A and
3 x 550 kVA N+1 Outlet B
- Outlet A in ESS mode.
- Outlet B in VMMS mode.
- Powerware Hot Sync® technology.
Author:
Article provided by Eaton Industries, SL